61
Errorcode Meaning Condition
DHWOutletThermistorOpenor
Short (Automaticrestore)
WhennoresponseatDHW Outlet
Thermistor,errorcode32will
appear.
Failureevent
When DHWOutletThermistor’swiringlinelocatedatDHWconnectionisdisconnected.
Checkpoint
②MeasureresistanceacrosstheDHWOut-
let Thermistorwithamulti-meter.Ifthemulti-
meterdisplays0Ω(shortcircuit),replacetheDHW
Thermistor.
①VerifythattheDHWOutletThermistorisproperlysecuredin
theDHWwaterconnection.VerifyproperconnectionoftheDHW
OutletThermistor'swiringtothecircuitboard.
(CN7:Yellow
,Yellow
)
Chapter4Troubleshooting
HotWaterOutlet(Yellow/Yellow)