Errorcode Meaning Condition
False󰘱amesensing
(Automaticrestore)
Iffalse󰘱ameisdetectedafter
combustionisendederrorcode39
willappear.
Failureevent
Aftercompletionofthewaterheatercombustion󰘱amedetectionsensordetectsIncasethe󰘱ame
generated.
Checkpoint
①checkthefrontcoverwillbeclosed.
Chapter4Troubleshooting
■FrommorethanDC2.5Vafterignitionsafetycut-o󰘯willappear
WhensettingbeforeignitionislessthanDC2.5V:Replace󰘱amesensor.
WhensettingbeforeignitionismorethanDC2.5V:Replacethe󰘱ameobservationglassandgasket.
ITEM NormalValue
Beforeignition MorethanDC2.5V
Afterignition LessthanDC2.5V