EasyManua.ls Logo

Rheem RUUD AdvantagePlus - Temperature Probe Resistance Chart; Thermistor Resistance Values

Rheem RUUD AdvantagePlus
16 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AdvantagePlus Fault Tree Troubleshooting
1706.doc
16
Temperature °F Resistance Temperature °F Resistance Temperature °F Resistance
70 11,884 111 4,564 151 2,003
71 11,593 112 4,467 152 1,966
72 11,308 113 4,370 153 1,928
73 11,031 114 4,277 154 1,891
74 10,764 115 4,185 155 1,855
75 10,501 116 4,096 156 1,820
76 10,249 117 4,008 157 1,786
77 10,000 118 3,923 158 1,752
78 9,762 119 3,840 159 1,719
79 9,526 120 3,759 160 1,687
80 9,300 121 3,681 161 1,656
81 9,078 122 3,603 162 1,625
82 8,862 123 3,529 163 1,594
83 8,653 124 3,455 164 1,565
84 8,448 125 3,383 165 1,536
85 8,251 126 3,313 166 1,508
86 8,056 127 3,244 167 1,480
87 7,869 128 3,178 168 1,453
88 7,685 129 3,112 169 1,426
89 7,507 130 3,049 170 1,400
90 7,333 131 2,986 171 1,375
91 7,164 132 2,926 172 1,350
92 6,999 133 2,866 173 1,326
93 6,838 134 2,809 174 1,302
94 6,683 135 2,752 175 1,278
95 6,530 136 2,697 176 1,255
96 6,383 137 2,643 177 1,233
97 6,238 138 2,590 178 1,211
98 6,098 139 2,539 179 1,190
99 5,961 140 2,488 180 1,169
100 5,827 141 2,439 181 1,148
101 5,698 142 2,391 182 1,120
102 5,571 143 2,343 183 1,108
103 5,449 144 2,297 184 1,089
104 5,327 145 2,253 185 1,070
105 5,210 146 2,209 186 1,052
106 5,095 147 2,166 187 1,033
107 4,984 148 2,124 188 1,016
108 4,876 149 2,083 189 998
109 4,769 150 2,043 190 981
110 4,666