EasyManuals Logo

Riello UPS CSS sentryum CBM User Manual

Riello UPS CSS sentryum CBM
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
- 9 -
POWER CONNECTION INFORMATION
INPUT AC Line Connection 3PH + N + PE
Table 6
CSS
size
[kVA]
Max
current
[A]
Terminal L1, L2, L3, N PE
Suggested wire L1, L2, L3, N, PE
(
*
)
Maximum
cross section
[sqmm]
Max Tightening
torque
[Nm]
Bolt
size
Cross sectional area
L1, L2, L3
[N x sqmm]
Cross sectional area
N, PE
(
**
)
[N x sqmm]
Type
10 21 10 1.9 M6 1 x 2.5 1 x 4
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15 31.5 16 3 M6 1 x 4 1 x 6
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20 40 16 3 M6 1 x 6 1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
BYPASS AC Line Connection 3PH + N + PE (Dual Input)
Table 7
CSS
size
[kVA]
Max
Continuous
current
[A]
Terminal L1B, L2B, L3B, N PE
Suggested wire L1B, L2B, L3B, N, PE
(
*
)
Maximum
cross section
[sqmm]
Tightening
torque
[Nm]
Bolt
size
Cross sectional area
L1B, L2B, L3B
[N x sqmm]
Cross sectional area
N, PE
(
**
)
[N x sqmm]
Type
10 16 10 1.9 M6 1 x 2.5 1 x 4
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15 24 16 3 M6 1 x 4 1 x 6
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20 32 16 3 M6 1 x 6 1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
OUTPUT AC Line Connection 3PH + N + PE
Table 8
CSS
size
[kVA]
Nominal
current In
[A]
Terminal L1, L2, L3, N PE
Suggested wire L1, L2, L3, N, PE]
(
*
)
Maximum
cross section
[sqmm]
Tightening
torque
[Nm]
Bolt
size
Cross sectional area
L1, L2, L3
[N x sqmm]
Cross sectional area
N, PE
(
**
)
[N x sqmm]
Type
10 14.5 10 1.9 M6 1 x 2.5 1 x 4
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15 22 16 3 M6 1 x 4 1 x 6
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20 29 16 3 M6 1 x 6 1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
Input Battery DC Line Connection BATT+, BATT-, BATT N, PE (Nominal voltage +240V, -240V)
Table 9
CSS
size
[kVA]
Rated Current [A]
Terminal
BATT +, BATT -, BATT N
PE
Suggested wire BATT +, BATT -, BATT N, PE
(
*
)
@nominal
battery
voltage
@end of
discharge
voltage
Maximum
cross section
[sqmm]
Tightening
torque
[Nm]
Bolt size
Cross sectional area
+, -, N, PE
(
**
)
[N x sqmm]
Type
10 22 27.5 10 1.9 M6 1 x 6
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15 33 41 16 3 M6 1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20 44 55 16 3 M6 1 x 16
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
(*)
The suggested cross section refers to 90°C rated cables with an ambient temperature of 30°C. If different cables are used, or
installed at a higher ambient temperature, the cable size needs to be reviewed.
The cross sections indicated in the table refer to a maximum length of 10 metres
(**)
We recommend using at least two PE connection cables. If only one cable is used, it must have a minimum section of 10 mm².

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Riello UPS CSS sentryum CBM and is the answer not in the manual?

Riello UPS CSS sentryum CBM Specifications

General IconGeneral
BrandRiello UPS
ModelCSS sentryum CBM
CategoryPower Supply
LanguageEnglish

Related product manuals