20068131
10
Technical description of the burner
4.6 Maximum dimensions
The dimensions of the burner are shown in Fig. 1.
Bear in mind that inspection of the combustion head requires the
burner to be opened and the rear part drawn back on the guides.
The dimensions of the open burner are indicated by position O.
Tab. E
(1) Blast tube: short-long
4.7 Firing rates
The maximum output is chosen within area A.
The minimum output must not be lower than the minimum limit
of the diagram:
RS 34/E MZ = 45 kW
RS 44/E MZ = 80 kW
mm A D E
F
(1)
HILONVM
RS 34/E MZ 442 422 508 216-351 140 305 138 780 84 177 1”1/2
RS 44/E MZ 442 422 508 216-351 152 305 138 780 84 177 1”1/2
The firing rate (Fig. 2) was obtained considering a
room temperature of 20°C and an atmospheric
pressure of 1013 mbar (approx. 0 m above sea
level), with the combustion head adjusted as
shown at page 24.
Fig. 2
D9304
Thermal power
Thermal power
Combustion chamber
pressure - mbar
Combustion chamber
pressure - mbar
RS 44/E MZ
RS 34/E MZ