Start-up, calibration and operation of the burner
6.6.2 Info mode
The Info mode (InFo) visualises general system information. To
access this level you must:
press the “i/reset” key for 1-3 s.
Release the key immediately when the display shows
“InFo”.
The list of parameters (in the sequence in which they are dis-
played) is shown in Tab. P.
Tab. P
6.6.3 Service mode
The Service mode (SEr) visualises the error log and certain
technical information about the system. To access this level you
must:
press the “i/reset” key for more than 3 s.
Release the key immediately when the display shows
“SEr”.
The list of parameters (in the sequence in which they are dis-
played) is shown in Tab. Q.
Tab. Q
6.6.3.1 Operating mode on Info Mode and Service Mode
After access to these levels, the display visualises the number of
the parameter (flashing) on the left, and the corresponding value
on the right.
If the value is not displayed, press the
“i/reset” key for 1 to 3 sec-
onds
To return to the Parameter List, press the
“i/reset” key for more
than 3 s, or press the keys
“+” and “-” (ESC) simultaneously.
To move on to the next parameter, press the
“+” or “i/reset” key
for less than 1 s. At the end of the list, the display visualises
“End”.
To move back to the previous parameter, press the key
“-”.
To return to the Normal/Standard Visualisation Mode, press the
“i/reset” key for more than 3 s, or press the keys “+” and “-”
(ESC) simultaneously.
For a moment the display will show
“OPErAte”.
No. Parameter
167
Volumetric delivery of fuel in the unit of measurement
selected
162 Operation time with flame
163 Operation time
164 No. of resettable ignitions
166 Total no. of ignitions
113 Identification code of the burner
107 Software version
108 Software variation
102 Control box test date
103 Identification code of the control box
104 Identification number of the group of parameters set
105 Version of the group of parameters
143 Reserved
End
No. Parameter
954 Flame intensity (%)
960 Actual fuel which passes in units of volume / h
(m³/h, l/h, ft³/h, gal/h)
121 Manual setting of output
Not defined = automatic operation
922 Position of the servomotors (expressed in de-
grees, symbol )
0 = fuel
1 = air
161 Number of errors
701
÷725
Log of the errors: 701-725.01, Code