EasyManua.ls Logo

Rivacold ST Series - Page 51

Rivacold ST Series
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ST-SP Pag. 51 Rev 02 05/13
UK
Code Level Descr. Range Unit MBP LBP HBP
List of -dEF defrosting parameters
dtY* 1 Defrosting type
0 = heating element: ends at temperature or after maximum safe time
(timeout)
1 = hot gas
: ends at temperature or after maximum safe time
(timeout)
For defrosting using a heating element, there is a 1 second delay
between the compressor switching off and the defrosting relay being
triggered
0,1 1 1 0
dit 1 Defrosting interval
The maximum time (from start to start) between two consecutive
defrosting cycles. When this time expires, a defrosting cycle is enabled
(cyclical defrosting). The timer is reset at each defrosting request (even
if not cyclical).
0 = cyclical defrosting disabled
0 … 250 h 6 6 6
dct 1 Defrosting interval count mode
0 = counts if the compressor is operating
1 = counts all the time
0,1 1 1 1
dOH 1 Defrosting start delay at power-on
The time, as from when the instrument is switched on, for which any
defrosting requests are frozen (manual defrosting excluded)
0 … 250 min 0 0 0
dEt* 1 Defrosting timeout
When the set time expires, defrosting is in any case ended, even if the
defrost end temperature has not been reached, passing on to the drip
phase
1 … 250 min 15 15 15
dSt* 1 Defrost end temperature
The probe 2 temperature above which defrosting is ended. If, at the
start of a defrosting cycle, the temperature is greater than that set, no
defrosting will be carried out. In the event of a probe 2 malfunction,
the defrosting cycle will in any case terminate after reaching a time
limit
-50.0 …
199.0
°C [°F] 10 15 10
dS2 1 Defrost end temperature for the second evaporator
The probe 3 temperature above which defrosting for the second
evaporator is ended. If, at the start of a defrosting cycle, the
temperature is greater than that set, no defrosting will be carried out.
In the event of a probe 3 malfunction, the defrosting cycle will in any
case terminate after reaching a time limit.
This function is only enabled if P01=3o4, Co4=3 and CP0=2 (alarm
relay used for second evaporator defrosting and probe 3 used to
detect the temperature of the second evaporator). In this case, the
dripping phase will begin after the defrosting cycles of both
evaporators have ended.
-50.0 …
199.0
°C [°F] 10 10 10
dPO 1 Defrosting at power-on
0 = disabled
1 = defrosting when the instrument is switched on
0,1 flag 0 0 0
List of -FAn fan parameters
FSt 1 Fans switch on temperature probe2 FSt: fans off
Fot probe2 < (FSt –
FAd): fans on
probe2 < (Fot – FAd): fans
off
-50.0 …
199.0
°C [°F] 8 -5 50
Fot 1 Fans switch off temperature
-50.0 …
199.0
°C [°F] -50 -50 -50
FAd 1 Fans switch on and off differential 1.0 …
90.0
°C [°F] 2 2 2
Fdt 1 Post-dripping time
The time after the dripping phase, during which the fans remain
switched off
0 … 60 min 1 2 0
dt 1 Dripping time
The time after a defrosting cycle during which the compressor and the
evaporator are stopped in order to favour evaporator dripping
0 … 60 min 2 2 0
dFd 1 Fans deactivated during defrosting
0 = fans activated (operation set from FPt)
1 = fans deactivated
0,1 flag 1 1 0
FCO 1 Fans activated with compressor off
0 = fans deactivated
1 = fans activated (operation set from FPt)
2 = fans in duty cycle operation
0 … 2 0 0 0
Fon 1 Fans ON time during duty cycle operation (FCO=2) 1 … 60 min 15 15 15
FoF 1 Fans OFF time during duty cycle operation (FCO=2) 1 … 60 min 15 15 15

Table of Contents