EasyManua.ls Logo

Rivacold ST Series - Faults Search

Rivacold ST Series
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ST-SP Pag. 59 Rev 02 05/13
UK
8
8
.
.
F
F
a
a
u
u
l
l
t
t
s
s
s
s
e
e
a
a
r
r
c
c
h
h
POSSIBLE CAUSES SOLUTIONS
A
The compressor does not start and does not release a humming sound
1 Lack of voltage. Start-up relay with open contacts.
2 Thermal cut-off intervenes.
3 Loose electrical connections or incorrect electrical connections.
1 Check the line or replace the relay.
2 Re-check the electrical connections.
3 Tighten or re-do the connections in accordance to the
wiring diagram.
B
The compressor does not start (releases humming sound) and the
thermal cut-off intervenes
1 Incorrect electrical connections.
2 Low voltage supply to the compressor.
3 Defective start-up of the condenser.
4 Relay does not close.
5 Winding of the electrical motor interrupted or in short-circuit.
1 Re-do the connections.
2 Identify the cause and eliminate it .
3 Identify the cause and replace the condenser.
4 Identify the cause and replace the relay if necessary.
5 Replace the compressor.
C
The compressor starts but the relay does not open
1 Incorrect electrical connections.
2 Low voltage supply to the compressor.
3 Relay blocked in closed position.
4 Excessive discharge pressure.
5 Winding of the electrical motor interrupted or in short-circuit.
1 Check the electrical circuit.
2 Identify the cause and eliminate it.
3 Identify the cause and eliminate it .
4 Identify the cause and replace the relay if necessary.
5 Replace the compressor.
D
Intervention of the thermal cut-off
1 Low voltage supply to the compressor (imbalanced phases on tri-
phase motors).
2 Defective thermal cut-off.
3 Defective running condenser.
4 Excessive discharge pressure.
5 Suction pressure too high.
6 Compressor overheated, hot return gas.
7 Winding of the compressor motor in short-circuit.
1 Identify the cause and eliminate it.
2 Check its characteristics and replace it if necessary.
3 Identify the cause and eliminate it .
4 Check the ventilation and any possible restrictions or
obstructions in the system circuit.
5 Check the sizing of the system. Replace the condensing
unit with a more powerful one, if necessary.
6 Check the refrigerant load; repair the potential loss and
add gas if necessary.
If the semi-machine does not have a safety valve, the load of
refrigerant gas must be lower than 10 kg.
7 Replace the compressor.
E
The compressor starts and circulates, with short-spanned function cycles
1 Thermal cut-off.
2 Thermostat.
3 Intervention of the high pressure meter, due to the insufficient
cooling of the condenser.
4 Intervention of the high pressure meter, due to the excessive load
of refrigerant gas.
5 Intervention of the low pressure meter, due to the scarce load of
refrigerant gas.
6 Intervention of the low pressure meter, due to the restriction or
clogging of the expansion valve.
1 See previous point (thermal cut-off intervention).
2 Small differential; correct adjustment .
3 Check that the motorized ventilator functions correctly or
clean the condenser.
4 Reduce the refrigerant load.
5 Repair the loss and add refrigerant gas.
If the
PARTLY COMPLETED MACHINERY does not have a safety valve, the
load of refrigerant gas must be lower than 10 kg.
6 Replace the expansion valve.
F
The compressor functions uninterruptedly or for long periods
1 Poor load of refrigerant gas.
2 Thermostat contacts blocked in closed position.
3 System insufficiently sized in function of the load.
4 Excessive load to cool or insufficient insulation.
5 Evaporator covered with ice.
6 Restriction in the system circuit.
7 Condenser clogged.
1 Repair the loss and add refrigerant gas.
If the
PARTLY COMPLETED MACHINERY does not have a safety valve, the
load of refrigerant gas must be lower than 10 kg.
2 Replace the thermostat.
3 Replace the system with a more powerful one.
4 Reduce the load and improve insulation, if possible.
5 Defrost.
6 Identify the resistance and eliminate it .
7 Clean the condenser.
G
Running condenser damaged, interrupted, or in short-circuit
1 Incorrect running condenser.
1 Replace the condenser with the correct type.
H
Start-up relay defective or burnt out
1 Incorrect relay.
2 Relay assembled incorrectly .
3 Incorrect running condenser.
1 Replace with the correct relay.
2 Reassemble the relay in the correct position.
3 Replace the condenser with the correct type.
I
Compartment temperature too high
1 Thermostat regulated too high.
2 Expansion valve under-sized.
3 Evaporator under-sized.
4 Insufficient air circulation.
1 Regulate correctly.
2 Replace the expansion valve with a suitable one.
3 Replace it increasing the surface of the evaporator.
4 Improve air circulation.

Table of Contents