Direct Digital Controller
90 Direct Digital Controller fw 4.013 – Ed. 01/2013
17 - If necessary repeat steps 12 - 17 -to complete the parameter settings for the selected category; then,
again if necessary, set the parameters of other categories, executing step 11 - and steps 12 - 17 - again.
18 - To exit, select
.
4.4.2.5.5 Robur Box water pumps delay
This parameter is used to set the switch-off delay on the common primary water pump on the separable plant
part, when managed by RB200; if the water pump is not configured, access to the parameter settings panel is
denied.
1 - Select
from the initial screen to gain access to the main menu.
2 - Select
to gain access to the System installation.
3 - If required, enter the installer password on the numerical keypad that appears on the display.
4 - Select “Plants” from the drop-down menu.
5 - Select the system for which the parameters are to be set:
for two-line cooling/heating plant;
for the hot water production plant;
6 - Turn the knob to scroll the cursor downward until highlighting “Splitt.Plant Part” and press the knob.
7 - Select “RBox W Pump Delay” from the drop-down menu.
8 - To modify the values set, position the cursor on the value to be modified.
9 - Press the knob to allow the change of the selected value.
10 - Turn the knob until the desired value is displayed.
11 - Press the knob to confirm the set value.