Direct Digital Controller
94 Direct Digital Controller fw 4.013 – Ed. 01/2013
12 - To exit, select .
4.4.2.6.2 Auxiliary boiler operation
To set the operating modes of the auxiliary boilers (only in heating or 2-line cooling/heating plant) proceed as
described below; for more information on the topic see paragraph 4.2 on page 55. and the Applications
Manual (code D-LBR630).
1 - Select
from the initial screen to gain access to the main menu.
2 - Select
to gain access to the System installation.
3 - If required, enter the installer password on the numerical keypad that appears on the display.
4 - Select “Plants” from the drop-down menu.
5 - Select the plant for which the differential is to be set:
for two-line cooling/heating plants, for
hot water production plants, or
for chilled water production plants.
6 - Turn the knob to scroll the cursor downward until highlighting “Base plant part” and press the knob.
7 - Select "Auxil. boiler operation" from the drop-down menu.
8 - Position the cursor on
next to the option that is to be set: "Complement" or "Complem.& Substit".
9 - Press the knob to activate the option. The
symbol indicates that the option has been enabled .
10 - When the “Complem. & Substit.” function is enabled the display shows the symbol
, selecting and
pressing the knob we can enable the “Progressive substitution” function.
11 - To exit, select
.
Selecting "Progressive substitution" also required:
Special plant configuration.
The presence of an additional temperature probe on the return manifold of the heat pump.
The setting of additional parameters in the regulation parameter settings panel (see 4.4.2.6.4 on
page 96).
Discuss the applicability of this option with the Robur Pre-Sales Service, before using it.
WARNING