Configure an EtherNet/IP Driver
For EtherNet/IP communication, you must use a 1768-ENBT or 
1768-EWEB module. If your controller is a 1768-L4xS, you must use a 
series B 1768-ENBT or 1768-EWEB module. You can install up to two 
of these modules to the left of the controller in the 1768 backplane. 
Before you can load controller firmware via the EtherNet/IP network, 
you must set the EtherNet/IP module’s IP address. You can set the IP 
address by using the BootP-DHCP Utility on the Tools menu in 
RSLogix 5000 software.
For more information, refer to the EtherNet/IP Modules in Logix5000 
Control Systems User Manual, publication ENET-UM001
.
Set the Communication Path to the Controller
1. Open an RSLogix 5000 project for the controller.
2. From the Communications menu, choose Who Active.
3. Expand the communication driver to the level of the 
controller.
4. Select the controller.
5. Complete the desired action.
To Click
Monitor the project in the controller Go Online
Transfer a copy of the project from the controller to RSLogix 5000 software Upload
Transfer the open project to the controller Download