Programming and Parameters 3-7
Display Group (continued)
d018 [Elapsed Run Time]
Accumulated time drive is outputting power. Time is displayed in 10 hour increments.
Values Default Read Only
Min/Max: 0/9999 Hrs
Display: 1 = 10 Hrs
d019 [Testpoint Data]
Related Parameter(s): A102
The present value of the function selected in A102 [Testpoint Sel].
Values Default Read Only
Min/Max: 0/FFFF
Display: 1 Hex
d020 [0-10V Analog Input]
Related Parameter(s): A110, A111
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).
Values Default Read Only
Min/Max: 0.0/100.0%
Display: 0.1%
d021 [4-20mA Analog Input]
Related Parameter(s): A112, A113
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
Values Default Read Only
Min/Max: 0.0/100.0%
Display: 0.1%