Programming and Parameters 3-17
Advanced Program Group (continued)
A079 [Jog Accel/Decel]
Sets the acceleration and deceleration time when a jog command is issued.
Values Default 10.0 Secs
Min/Max: 0.1/600.0 Secs
Display: 0.1 Secs
A080 [DC Brake Time]
Related Parameter(s): A081
Sets the length of time that DC brake current is injected into the motor. Refer to parameter A081 [DC
Brake Level].
Values Default 0.0 Secs
Min/Max: 0.0/90.0 Secs
Display: 0.1 Secs
A081 [DC Brake Level]
Related Parameter(s): P037, A080
Denes the maximum DC brake current, in amps, applied to the motor when P037 [Stop Mode] is set
to either Ramp or DC Brake.
Values Default Drive Rated Amps × 0.05
Min/Max: 0.0/(Drive Rated Amps × 1.8)
Display: 0.1 Amps
DC Injection Brakin
g
Mod
e
V
olts/S
p
eed
Volta
g
e
Tim
e
Stop Comman
d
Spee
d
[
DC Brake Level
]
DC Brake Time
V
olts/S
p
eed
Ram
p
-to-Sto
p
Mod
e
Tim
e
Stop Comman
d
[
DC Brake Level
]
DC Brake Time
Voltage
Speed
!
ATTENTION: If a hazard of injury due to movement of equipment or material exists,
an auxiliary mechanical braking device must be used.
!
ATTENTION: This feature should not be used with synchronous or permanent
magnet motors. Motors may be demagnetized during braking.
userman.book Page 17 Friday, June 21, 2002 2:48 PM