English-10 PowerFlex 400P Adjustable Frequency AC Drive Quick Start
I/O Terminal Block Specifications
(2)
Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.
Refer to the PowerFlex 400P User Manual for maximum control cable
length recommendations.
I/O Wiring Recommendations
Wire Type(s) Description Minimum
Insulation Rating
Belden 8760/9460
(or equiv.)
0.8 mm
2
(18AWG), twisted pair, 100%
shield with drain.
(1)
(1)
If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.
300V
60 degrees C
(140 degrees F)
Belden 8770
(or equiv.)
0.8 mm
2
(18AWG), 3 conductor, shielded for
remote pot only.
Frame Maximum Wire Size
(2)
Minimum Wire Size
(2)
Torque
All 1.3 mm
2
(16 AWG) 0.13 mm
2
(26 AWG) 0.5-0.8 N-m (4.4-7 lb.-in.)