8 SLC 500 8-Point Analog Output Module
Publication 1746-IN026A-EN-P - July 2003
Installation
Install the SLC 500 system in a properly rated (i.e., NEMA) enclosure. Make sure
that the SLC 500 system is properly grounded.
Choosing a Slot in the Chassis
Two factors determine where the analog module should be located in the chassis:
ambient temperature and electrical noise. Consider the following conditions when
selecting a slot for an analog module. Position the module:
in a slot away from an ac or high voltage dc modules
in the chassis closest to the bottom of the enclosure where the SLC 500
system is installed
away from the chassis power supply if installed in a modular system
Prevent Electrostatic Discharge
TIP
To use the advanced features of Class 3 operation, an SLC 5/02
or higher processor must be used, and the module must be
located in the local chassis or in a remote ControlNet chassis
with a 1747-ACN(R)15 adapter.
If the module is located in remote I/O chassis with a 1747-ASB
adapter, it will operate in Class 1 mode, and you must use
block transfer for configuration and data retrieval.
TIP
Remember that, in a modular system, a processor or adapter
always occupies the first slot of the chassis.
ATTENTION
!
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow these
guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley SLC 500 and is the answer not in the manual?

Rockwell Automation Allen-Bradley SLC 500 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley SLC 500
CategoryControl Unit
LanguageEnglish

Related product manuals