A065 [Analog Out Sel] 0/23 1 0
A066 [Analog Out High] 0/800% 1% 100%
A067 [Accel Time 2] 0.0/600.0 Secs 0.1 Secs 20.0 Secs
A068 [Decel Time 2] 0.1/600.0 Secs 0.1 Secs 20.0 Secs
A069 [Internal Freq] 0.0/400.0 Hz 0.1 Hz 0.0 Hz (for IP66,
NEMA/UL Type
4X drives)
60.0 Hz (for
IP20 drives)
A070
A071
A072
A073
A074
A075
A076
A077
[Preset Freq 0]
(1)
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
[Preset Freq 4]
[Preset Freq 5]
[Preset Freq 6]
[Preset Freq 7]
0.0/400.0 Hz 0.1 Hz 0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
(1)
To activate [Preset Freq 0] set P038 [Speed Reference] to option 4.
A078 [Jog Frequency] 0.0/[Maximum Freq] 0.1 Hz 10.0 Hz
A079 [Jog Accel/Decel] 0.1/600.0 Secs 0.1 Secs 10.0 Secs
A080 [DC Brake Time] 0.0/99.9 Secs 0.1 Secs 0.0 Secs
A setting of 99.9 Secs = Continuous
A081 [DC Brake Level] 0.0/(Drive Amps × 1.8) 0.1 Amps Amps × 0.05
A082 [DB Resistor Sel] 0/99 0 = “Disabled”
1 = “Normal RA Res”
2 = “NoProtection”
3-99 = % of Duty Cycle
0
A083 [S Curve %] 0/100% 1% 0% (Disabled)
No. Parameter Min/Max Display/Options Default
Option Output Range Minimum Output Value
Maximum Output Value
[Analog Out High] DIP Switch Position
0 “OutFreq 0-10” 0-10V 0V = 0 Hz P035 [Maximum Freq] 0-10V
1 “OutCurr 0-10” 0-10V 0V = 0 Amps 200% Drive Rated FLA 0-10V
2 “OutVolt 0-10” 0-10V 0V = 0 Volts 120% Drive Rated Output Volts 0-10V
3 “OutPowr 0-10” 0-10V 0V = 0 kW 200% Drive Rated Power 0-10V
4 “TstData 0-10” 0-10V 0V = 0000 65535 (Hex FFFF) 0-10V
5 “OutFreq 0-20” 0-20 mA 0 mA = 0 Hz P035 [Maximum Freq] 0-20 mA
6 “OutCurr 0-20” 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
7 “OutVolt 0-20” 0-20 mA 0 mA = 0 Volts 120% Drive Rated Output Volts 0-20 mA
8 “OutPowr 0-20” 0-20 mA 0 mA = 0 kW 200% Drive Rated Power 0-20 mA
9 “TstData 0-20” 0-20 mA 0 mA = 0000 65535 (Hex FFFF) 0-20 mA
10 “OutFreq 4-20” 4-20 mA 4 mA = 0 Hz P035 [Maximum Freq] 0-20 mA
11 “OutCurr 4-20” 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
12 “OutVolt 4-20” 4-20 mA 4 mA = 0 Volts 120% Drive Rated Output Volts 0-20 mA
13 “OutPowr 4-20” 4-20 mA 4 mA = 0 kW 200% Drive Rated Power 0-20 mA
14 “TstData 4-20” 4-20 mA 4 mA = 0000 65535 (Hex FFFF) 0-20 mA
15 “OutTorq 0-10” 0-10V 0V = 0 Amps 200% Drive Rated FLA 0-10V
16 “OutTorq 0-20” 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
17 “OutTorq 4-20” 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA 0-20 mA
18 “Setpnt 0-10” 0-10V 0V = 0% 100.0% Setpoint Setting 0-10V
19 “Setpnt 0-20” 0-20 mA 0 mA = 0% 100.0% Setpoint Setting 0-20 mA
20 “Setpnt 4-20” 4-20 mA 4 mA = 0% 100.0% Setpoint Setting 0-20 mA
21 “MinFreq 0-10” 0-10V 0V = Min. Freq P035 [Maximum Freq] 0-10V
22 “MinFreq 0-20” 0-20 mA 0 mA = Min. Freq P035 [Maximum Freq] 0-20 mA
23 “MinFreq 4-20” 4-20 mA 4 mA = Min. Freq P035 [Maximum Freq] 0-20 mA
Input State
of Digital In 1
(I/O Terminal 05)
Input State
of Digital In 2
(I/O Terminal 06)
Input State
of Digital In 3
(I/O Terminal 07)
Frequency Source Accel / Decel Parameter Used
(2)
0 0 0 [Preset Freq 0] [Accel Time 1] / [Decel Time 1]
1 0 0 [Preset Freq 1] [Accel Time 1] / [Decel Time 1]
0 1 0 [Preset Freq 2] [Accel Time 2] / [Decel Time 2]
1 1 0 [Preset Freq 3] [Accel Time 2] / [Decel Time 2]
0 0 1 [Preset Freq 4] [Accel Time 1] / [Decel Time 1]
1 0 1 [Preset Freq 5] [Accel Time 1] / [Decel Time 1]
0 1 1 [Preset Freq 6] [Accel Time 2] / [Decel Time 2]
1 1 1 [Preset Freq 7] [Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.
See the PowerFlex 40 User Manual for more information on parameters.
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell PowerFlex 40 and is the answer not in the manual?

Rockwell PowerFlex 40 Specifications

General IconGeneral
BrandRockwell
ModelPowerFlex 40
CategoryController
LanguageEnglish

Related product manuals