SPECIFICATIONS
DC Voltage
(Auto-ranging)
Input Impedance: 10MΩ
Maximum Input: 600V dc rms.
4 5
Autoranging Multimeter/English Autoranging Multimeter/English
The instrument complies with: EN61010-1.
Insulation: Class2, Double insulation.
Overvoltage category: CATIII 600V
Display: 2000 counts LCD display with function indication.
Polarity: Automatic, (-) negative polarity indication.
Overrange: “OL” mark indication.
Low battery indication: The “BAT” is displayed when the battery voltage
drops below the operating level.
Measurement rate: 2 times per second, nominal.
Auto power off: Meter automatically shuts down after approx. 15
minutes of inactivity.
Operating environment: 0 °C to 50 °C (32 °F to 122 °F) at < 70 %
relative humidity.
Storage temperature: -20 °C to 60 °C (-4 °F to 140 °F) at < 80 % relative
humidity.
For inside use, max height: 2000m
Pollution degree: 2
Power: One 9V battery , NEDA 1604, IEC 6F22.
Dimensions: 150 (H) x 70 (W) x 48 (D) mm
Weight: Approx.: 255g.
Accuracy is given at 18 °C to 28 °C (65 °F to 83 °F), less than 70 % RH.
Measurement
Category
Application
Ⅰ
Measurements on circuits not directly connected to mains.
Examples include: Measurements on battery powered
equipment and specially protected (internal) mains-derived
circuits.
Ⅱ
Measurements on circuits directly connected to the low
voltage installation.
Examples include: Household appliances, portable tools and
similar equipment.
Ⅲ
Measurements performed in the building installation.
Examples include measurements on distribution boards,
junction boxes, socket-outlets and wiring and cables in the
fixed installation.
Ⅳ
Measurements performed at the source of the low-voltage
installation. Examples include measurements on primary
overcurrent protection devices and electricity Instruments
+1.0% of rdg + 2 dgts