MODEL 82602-F79A-LCD/82602B-F79B-LCD/82604-F82A-LCD/82604B-F82B-LCD
15
time.
Regenerati
on Time
02:00
00:0023:59
Suit for A-01/03/11/13/21
Interval
Backwash
Times
00
020
Interval backwash times. For
example, F-01:indicate service 2
times, backwash 1 time (Only for
A-11/12/13)
Rinsing
Frequence
00
020
Rinsing added time. For example,
F-01:indicate rinse 2 times, service 1
time (Only for A-21)
Water
Treatment
Capacity
10m
3
099.99 m
3
Water treatment capacity in one circle
(m
3
) forA-01/02/03/11/12/13
Backwash
Time
10min
09959
Backwash time (minute)
Brine &
Slow
Rinse
Time
60min
09959
Brine & slow rinse time (minute)
Brine Refill
Time
5min
09959
Brine refill time (minute)
Fast Rinse
Time
10min
09959
Fast rinse time(minute)
Maximum
Interval
Regenera-
tion Days
30
040
Regenerate on the day even though
the available volume of treated water
do not drop to zero (0).
Output
Control
Mode
01
01 or 02
Mode 01: Signal turn on start of
regeneration and shut off end of
regeneration. (Connection refer to the
Figure P4)
Mode 02: Signal available only
intervals of regeneration cycles and
in service. (Connection refer to the
Figure P4)