MODEL:F67Q/F71Q/F68Q/F69Q/F116Q/F117Q
54
C. Air in resin tank.
D. Floccules in resin tank
during up-flow
C. Check and find the reason.
D. Clean t
tank.
12. Water
flows out
from drain or
after
regeneration.
A. Foreign material in valve
which makes valve can’t be
closed completely.
valve body.
high which results in valve
not getting the right status.
D. When in backwash
status, drain line is
communicated
A. Clean foreign material in valve
body.
B. Change valve core or sealing
ring.
C. Reduce water pressure or use
pressure release function.
D. Add check valve or solenoid
valve in the outlet, or
controller in the brine tank.
Control Valve Fault (Continue)
outflow pipe.
A. Foreign material in
injector or injector fails to
work.
shut-off.
C. Time of fast rinse too
short.
A. Clean and repair injector.
B. Repair brine valve and clean it.
C. Extend fast rinse time.
14. Circle
capacity
decreases.
A. Regenerate not properly.
B. Fouled resin bed or
polluted.
C. Salt setting is not proper.
D. Softener setting is not
proper.
deteriorated.
F. Turbine
gotten stuck.
A. Regenerate according to right
way.
B. Increase backwash flow rate
and time, clean or change resin.
C. Readjust brine drawing time.
D. According to the test of outlet
water, recount and reset.
E. Regenerate unit by manual
temporary then reset regeneration
cycle.
F. Disassemble flow meter and
clean it or replace a new flow
meter.