CRC–ECM
CRC–ECM version
Carisma
115
0,77
0,56
0,78
3,2
2,6
7,0
30
21
1 (E)
MIN
160
1,06
0,78
1,08
5,5
4,7
8,8
36
27
3
MED
210
1,32
0,98
1,37
8,0
7,1
11,0
41
32
5 (E)
260
1,57
1,19
1,65
11,0
9,9
14,6
47
38
7,5
MAX
325
1,86
1,42
1,98
14,8
13,6
21,0
51
42
10 (E)
200
1,43
1,03
1,42
4,0
3,1
6,0
30
21
1 (E)
MIN
265
1,83
1,34
1,83
6,1
4,9
9,0
36
27
3
MED
340
2,27
1,67
2,30
8,9
7,3
12,0
42
33
5 (E)
415
2,71
2,02
2,77
12,3
10,2
17,0
47
38
7,5
MAX
505
3,17
2,39
3,32
16,1
13,7
25,0
51
42
10 (E)
290
2,05
1,48
2,02
8,2
6,6
7,0
33
24
1 (E)
MIN
375
2,59
1,89
2,59
12,4
10,3
10,0
38
29
3
MED
475
3,19
2,34
3,23
17,8
15,1
15,0
44
35
5 (E)
590
3,84
2,84
3,93
24,8
21,4
22,0
49
40
7,5
MAX
720
4,51
3,38
4,68
33,0
29,1
32,0
54
45
10 (E)
380
2,61
1,90
2,57
7,3
5,9
9,0
37
28
1 (E)
MIN
475
3,20
2,34
3,17
10,5
8,6
13,0
43
34
3
MED
585
3,82
2,82
3,84
14,3
12,0
18,5
48
39
5 (E)
735
4,61
3,44
4,66
20,0
16,9
28,5
53
44
7,5
MAX
875
5,30
3,99
5,43
25,6
22,0
41,0
57
48
10 (E)
575
3,59
2,69
3,76
6,3
5,6
16,0
44
35
1 (E)
MIN
755
4,49
3,40
4,81
9,3
8,7
25,0
50
41
3
MED
910
5,21
3,99
5,63
12,1
11,4
41,0
55
46
5 (E)
1145
6,18
4,81
6,84
16,4
16,1
65,0
60
51
7,5
MAX
1365
7,04
5,53
7,93
20,8
20,9
99,0
64
55
10 (E)
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m
3
room and a reverberation time of 0.5 sec.
EUROVENT Certification
m
3
/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 64CRC−ECM 44CRC−ECM 24
m
3
/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 94CRC−ECM 74
eCM units with 4 Row Coil
COOLING
Entering air temperature + 27°C d.b. + 19°C w.b.
Water temperature + 7°C E.W.T. + 12°C L.W.T.
HEATING
Entering air temperature + 20°C
Water temperature + 45°C E.W.T. + 40°C L.W.T.
2 pipe units.
The following standard rating conditions are used:
www.eurovent-certification.com