CRC–ECM
CRC–ECM version
Carisma
120
0,73
0,55
0,71
2,3
1,0
7,0
30
21
1 (E)
MIN
170
0,97
0,74
0,91
3,8
1,6
9,0
36
27
3
MED
220
1,18
0,92
1,08
5,4
2,1
11,0
41
32
5 (E)
270
1,37
1,09
1,24
7,2
2,7
14,5
47
38
7,5
MAX
330
1,59
1,28
1,43
9,4
3,5
21,0
51
42
10 (E)
210
1,41
1,03
1,29
7,3
3,6
6,0
30
21
1 (E)
MIN
280
1,80
1,33
1,57
11,5
5,2
9,0
36
27
3
MED
350
2,18
1,64
1,85
16,0
6,9
12,0
42
33
5 (E)
430
2,57
1,95
2,13
21,6
8,8
17,0
47
38
7,5
MAX
515
2,95
2,26
2,41
28,1
11,0
25,0
51
42
10 (E)
305
1,96
1,46
1,76
6,4
1,2
7,0
33
24
1 (E)
MIN
395
2,44
1,83
2,10
9,6
1,7
10,0
38
29
3
MED
495
2,93
2,22
2,45
13,2
2,2
15,0
44
35
5 (E)
610
3,44
2,64
2,83
17,7
2,9
22,0
49
40
7,5
MAX
735
3,96
3,08
3,22
23,3
3,6
32,0
54
45
10 (E)
400
2,60
1,92
2,33
9,7
2,4
9,0
37
28
1 (E)
MIN
500
3,13
2,33
2,72
13,8
3,1
13,0
43
34
3
MED
610
3,68
2,77
3,12
18,4
4,0
18,5
48
39
5 (E)
755
4,36
3,32
3,63
24,8
5,2
28,5
53
44
7,5
MAX
890
4,94
3,80
4,06
31,8
6,3
41,0
57
48
10 (E)
605
3,45
2,63
2,99
8,9
3,7
16,0
44
35
1 (E)
MIN
785
4,22
3,28
3,58
12,7
5,1
25,0
50
41
3
MED
945
4,82
3,79
4,05
16,1
6,3
41,0
55
46
5 (E)
1175
5,60
4,49
4,69
21,1
8,2
65,0
60
51
7,5
MAX
1395
6,26
5,10
5,24
25,9
9,9
99,0
64
55
10 (E)
EUROVENT Certification
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m
3
room and a reverberation time of 0.5 sec.
m
3
/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 63+1CRC−ECM 43+1CRC−ECM 23+1
m
3
/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 93+1CRC−ECM 73+1
eCM units with 1 Row additional Coil
4 pipe units.
The following standard rating conditions are used:
www.eurovent-certification.com
COOLING
Entering air temperature + 27°C d.b. + 19°C w.b.
Water temperature + 7°C E.W.T. + 12°C L.W.T.
HEATING
Entering air temperature + 20°C
Water temperature + 65°C E.W.T. + 55°C L.W.T.