CV10
Quick Start Guide
SEPTEMBER 2004 8
Step-by-Step Procedure for Step 3
a) Enter the drive Operating Mode in parameter 0-00.
0-00 = 0000 Vector (General Purpose) “Default Setting”.
0-00 = 0001 Vector (Variable Torque).
0-00 = 0002 Volts / Hz.
b) If a value of 0002 (Volts/Hz) was entered for parameter 0-00, then skip to step K.
c) Enter Motor Rated Voltage from motor nameplate in parameter 0-01.
d) Enter Motor Rated Current from motor nameplate in parameter 0-02.
e) Enter Motor Rated Kilowatts (kW=HPx.746) from motor nameplate in parameter 0-03.
f) Enter Motor Rated Speed (RPM) from motor nameplate in parameter 0-04.
g) Enter Motor Rated Frequency from motor nameplate in parameter 0-05.
h) Set parameter 0-06 equal to 0001 (enable auto tuning). Press the key and the auto tuning
function will start and the display will read " - At -".
i) The motor will not rotate during the auto tuning process but voltage will be applied to the motor.
j) When the auto tuning is successful, the display will read parameter 0-06. Otherwise an auto
tuning error will be displayed. Press the key until the display reads "5.00" (frequency
reference). Setup is completed. Skip the remaining steps K through O).
k) For Volts / Hz Operation, Select a pattern in parameter 10-0 = 0-18 (See page 73-75 of the
instruction manual for more detailed information) each pattern selects default values for
parameters 10 - 1 through 10-9. These values may require tuning to meet your application speed
and torque requirements.
l) Parameter 10-0 = 18, allows for a custom Volts/Hz pattern to be entered in parameters 10-4 to
10-9 to meet specific applications. Refer to page 73 of the instruction manual.
m) If the motor rated frequency is not 50 or 60 Hertz, adjust parameter 10 - 4 to the desired motor
rated frequency.
n) If you wish to operate the motor at a frequency higher than the motor rated frequency, adjust
parameter 3-00 to the maximum frequency desired.
o) Press the key until the display reads "5.00" (frequency reference). Setup is now
completed.
Step 4 Check Motor Rotation
• Press RUN key (FWD LED should light), motor should start running, and the digital operator should
display a value increasing from 00.00 to 05.00.
• Check Motor Rotation.
If the motor does not rotate in the correct direction:
Press STOP key. Remove AC power. Wait for LED "charge" lamp to extinguish.
Reverse motor leads T1 and T2. Restart the drive and check the rotation.
• Press STOP key to stop the drive.