PDM20 Series
-29-
Function
code
Description Set range Unit Default
Display
level
Modifi
cation
level
Notes
P1.03
Sensor
range
0.1
500.0
bar 10 Same as P0.03
P1.04
Sensor
feedback
type
0Voltage
feedback
1Current
feedback
1 Same as P0.04
P1.05
power
setting of
sensor
0.025.0
V25.0 Same as P0.05
P1.06
Upper limit
of running
frequency
P1.07
60.00
Hz 50.00
P1.07
Lower limit
of running
frequency
0.0
P1.06
Hz 0.00
P1.08
Action
choices
when
running
frequency
is lower
than lower
limit
frequency
02
2
0Run at lower limit
frequency
1Stop
2Standby
P1.09
Carrier
frequency
setting
1.015.0
kHz
Set by
model
The value can be
adjusted properly to
adjust motor noise