EasyManua.ls Logo

SAJ PDM20 series - Page 35

SAJ PDM20 series
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PDM20 Series
-34-
4.6 Programming Description of Parameters
P0.00 Pressure setting
0.0P0.03
bar 3.0
P0.03 Sensor range 0.0200.0 bar 10.0
The maximum range
of sensor
P0.04 Sensor feedback type
0Voltage feedback
1Current feedback
1
P0.05 Power setting of sensor
0.024.0
V10.0
P0.03 is the range of the sensor. Common range is 1MPa, namely 10.0bar.
P0.00 is the pressure value of the pipe network. If P0.00=3.0bar, after the smart
pump drive is started, the pressure of the pipe network keeps constant at 3.0 bar.
General sensor is in current type. The wiring method of SPD is similar to
pressure transmitter, connected to AI terminal as pressure feedback: if voltage
sensor is use, please modify P0.04 to 0. The wiring method of SPD is similar to
transmissible pressure gauge, connected to AI terminal as pressure feedback.
Note: because working voltage of sensor is different, before using, set working
power source of the sensor by P0.05; besides, make sure test result is precise. Set
range of the sensor P0.03 according to sensor parameters.
When feedback value is smaller than or equal to set pressure minus PID start
pressure
P0.00-P0.01
, and it holds the state in P0.10 set time, PID adjustment
will be restarted. For example, when P0.00=3
P0.01=0.3
P0.10=5.0, if feedback
value is smaller than or equal to 2.7, and the time is longer than 5s, PID adjustment
will be restarted. Once it is larger than 2.7, the time will recount.
P0.01 Start pressure deviation 0.0P0.00 bar 0.3
The value that is lower
than PID set pressure
P0.10
PID wakeup detection
delay
0.0120.0 s 1.0
PID wakeup detection
delay

Related product manuals