PDM20 Series
-36-
P0.08 PID sleep choices 022
0Sleep invalid
1Sleep mode 1
2Sleep mode 2
P0.09
PID sleep detection
delay
0.0
120.0
s1.0
In small water consumption, if
sleeping is slow or it can’t sleep,
make the value smaller; if it sleeps
in advance or it starts and stops
frequently, make the value bigger.
P0.10
PID wakeup detection
delay
0.0
120.0
s 1.0 PID wakeup detection delay
P0.11
PID sleep low level hold
frequency
0.00
60.00
Hz 35.00
PID runs at sleep low level hold
frequency. After the time of P0.12,
PID sleeps.
P0.12
Running time at PID
low level hold
frequency
0.00
3600
s3.0
P0.13
PID sleep deviation
pressure
0.0
P0.01
bar 0.1
If feedback pressure is in sleep
deviation range, start sleeping
treatment.