P0.39 Parameter lock function
01
0
After setting parameters, if you don’t want them to be modified by misoperation,
make P0.39= 1. At this time, parameters can only be monitored, but not be
modified. Only when P0.39 is modified to 0, can parameters be modified.
P0.40 Current fault type
029
Record fault type of the SPD. 0 means no fault. 1
29 refers to E001
E029. For
more details, please refer to fault inspection and troubleshooting chapter.
P1.34
Start/stop signal
choices
01
0
0Start/stop by keyboard
1Start/stop by terminals
P0.43
Frequency source
choices
08
8
0Digital setting
17Reserved
8Water supply PID
Each SPD can choose different start/stop modes and frequency sources.
P1 group parameters have the same meaning as P0 group. Please refer to P0 group
for more details.
P1.06 Upper limit frequency
P1.0760.0
Hz 50.00
P1.07 Lower limit frequency
0.00P1.06
Hz 0.00
P1.08
Action choices when
running frequency is lower
than lower limit frequency
0Run at lower limit frequency
1Stop
2Standby
2