PDS33 Series
- 31 -
Function
Code
Function
Description
Unit
Factory
setting
Modification
Type
Communicati
on Address
frequency
type
F0.18
Acceleration
time 1
0.0s ~ 6500.0s
0.1s
Due to
type
○
F012
F0.19
Deceleration
time 1
0.0s ~ 6500.0s
0.1s
Due to
type
○
F013
F0.20
Default setting
0:Not restore to default
setting
1: Restore to factory
setting
2:Fault record clearing
1
0
●
F014
F2 Group:Motor Parameters
F2.01
Motor rate
power
0.1KW ~ 400.0KW
0.1KW
Due to
type
●
F201
F2.02
Motor rate
voltage
1V ~ 440V
1V
Due to
type
●
F202
F2.03
Motor rate
current
0.01A ~ 655.35A
(<=55KW)
0.1A ~ 6553.5A
(>55KW)
0.01A/
0.1A
Due to
type
●
F203
F2.04
Motor rate
frequency
0.01Hz ~Max
frequency
0.01Hz
Due to
type
●
F204
F2.05
Motor rate
speed
1rpm ~ 36000rpm
1rpm
Due to
type
●
F205
F4 Group:VF control
F4.00
V/F curve
setting
0:Straight line V/F
curve
2:2.0th power low torque
V/F curve
1
2
●
F400
F4.01
Torque boost
0.1% ~ 30.0%
0.1%
Due to
type
○
F401
F4.02
Cut-off
frequency
0.00Hz~F0.10
0.01Hz
50.00Hz
○
F402
F5 Group:Input Terminals
F5.00
Function of
DI1
0:No function
1:Forward run(FWD)
4:Forward JOG(FJOG)
1
1
●
F500
F5.01
Function of
DI2
1
4
●
F501