7.3.15.3. Dampers
Menu » Service » Dampers
NO. LABEL
1 Supply / extract damper
2 Recirculation damper
3 Fire damper
7.3.15.3.1. Supply / Extract damper
Menu » Service » Dampers » Supply / Extract damper
NO. LABEL DESCRIPTION
1 Type
Options
• None
• On/O
• 3P
• Open/Close
2 Open time Range: [ 0 .. 255 seconds ]
7.3.15.3.2. Recirculation damper
Menu » Service » Dampers » Recirculation damper
NO. LABEL DESCRIPTION
1 Recirculation damper
Options:
• Disabled
• Enabled
2 Open time Range: [ 0 .. 255 seconds ]
3 Recirculation by set point
Options:
• Disabled
• Enabled
7.3.15.3.3. Fire damper
Menu » Service » Dampers » Fire damper
NO. LABEL DESCRIPTION
1 Type
Options:
• None
• One switch
• Two switches
2 Open time Range: [ 0 .. 255 seconds ]
3 Testing
Options:
• Disabled
• Enabled
4 Testing days interval Range: [ 1 .. 120 days ]
5 Action on re alarm
Options:
• Open
• Close