7.3.15.4. Heat exchanger
Menu » Service » Heat exchanger
NO. LABEL
1 Type
2 Frost protection
7.3.15.4.1. Type
Menu » Service » Heat exchanger » Type
NO. LABEL DESCRIPTION
1 Heat exchanger
Options:
• None
• Plate
• Rotor
2 Type
Options:
• 0-10VDC
• On/O
3 Output threshold Range: [ 0 .. 100 % ]
4 Prot. By RPM
Options:
• Enabled
• Disabled
5 Service timer limit Range: [ 1 .. 1000 days ]
6 Bypass open/close limit Range: [ 0 .. 100 % ]
7 Bypass open time Range: [ 0 .. 255 seconds ]
7.3.15.4.2. Frost protection
Menu » Service » Heat exchanger » Frost protection
NO. LABEL
1 Activation
2 Deactivation
3 Protections
7.3.15.4.2.1. Activation
Menu » Service » Heat exchanger » Frost protection » Activation
NO. LABEL DESCRIPTION
1 Outdoor air temperature
Options:
• Active
• Inactive
2 Outdoor air temperature Range: [ -40 .. -0.1 °C ]
3 Exhaust air temperature
Options:
• Active
• Inactive
4 Exhaust air temperature Range: [ 0.1 .. 10 °C ]
5 Dierence from frost point
Options:
• Active
• Inactive
6 Dierence from frost point Range: [ 0.1 .. 10 °C ]