Installation - Device Parameters
DX FUNCTION SYSTEM SETTING DEFINITION DEFAULT
D01 Heating 0 Pulse Width Modulation
Control 1 On-O 0.5 Deg C +/- 0.25 Deg C 0
2 On-O 1.0 Deg C +/- 0.5 Deg C
D02 Room -3.0 to 3.0 Temperature Oset from
Temperature Deg C Measured Temperature to 0 Deg C
Oset Compensate for any error
D03 Sensor probe or 0 Sensor/Cyl stat not Connected
Cylinder thermostat 1 Sensor/Cyl stat Connected 0
connection
D04 Sensor probe 0 D03 must be set to 1 then
used as air sensor external sensor be used as
or oor sensor Air sensor. There will be no
internal temp measurement
0
1 D03 must be set to 1 then
external sensor used for oor
protection. Internal temp is
measured by stat
D05 Cooling Control 1 On-O 0.5 Deg C +/- 0.25 Deg C
2
2 On-O 1.0 Deg C +/- 0.5 Deg C
D06 Actuator type 0 NO Normally Open
1
1 NC Normally Closed
D07 Valve protection 0 Disable
1
1 Enable
VS10W and VS10B Installer Manual 41
INSTALLATION