EasyManua.ls Logo

Sames GNM 100 - Storing the Set Points; Using the Values Stored; Triggering the High Voltage

Sames GNM 100
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Index revision : C 12 6209
To change the current set point, press key 2 or 3
. The display will, for example, indicate:
4.4. Storing the set points
The GNM 100 can memorise 9 U and I value tables preset by the user as needed. These tables are ref-
erenced from J1 to J9.
To create a table:
The gun trigger must be released.
Adjust the high voltage (Vc) and the current limitation (Il) set point values according to the proce-
dure described in paragraph3.3, then press key .
the display will, for example, indicate:
Choose a table (from J1 to J9) by pressing keys 2
or 3 (for example J2).
Press key for three seconds. The U and I values
are stored in the table J2.
4.5. Using the values stored
When, for example, the display indicates:
Choose a table (from J1 to J9) by pressing keys 2
or 3 .
The set point values of the high voltage and the cur-
rent limitation used are memorised in the table cho-
sen.
4.6. Triggering the high voltage
The trigger has to be puller for the gun to be powered.
The display takes the form of a bar graph, indicating the high voltage and current values, for example:
Displayed at the end of each bar graph is the volt-
age value at the gun electrode (in kilovolts) and the
current debited by the gun's high voltage electrode
(in micro amps).
The position of the symbol (*) at the end of the bar graph indicates whether the module works by a high
voltage regulation or by a current limitation.
If no table is used when the trigger is pulled, the high voltage and current set point values can be modified
by pressing keys 2 or 3 .
If a table from J1 to J9 is used when the trigger is pulled, the values cannot be changed.
When the trigger is released for more than 3 seconds, the last value read is displayed.