APPENDIX A
4.4 PROGRAMMING INFORMATION FOR PARAMETER GROUP NO.1 – CHARGE CURVE
4.4.1 Programming Ranges & Default Values of Parameters Under Parameter
Group No.1 - Charge Curve
Table 4.1 below gives details of programming ranges and default values of parameters under Parameter Group No.1 -
"CHARGE CURVE". Refer to the Menu Map in Fig 4.1 (Section 4.1) for navigating through various parameters under
this Parameter Group No.1.
TABLE 4.1 PROGRAMMING INFORMATION FOR PARAMETER GROUP NO.1 – CHARGE CURVE
Parameter
Setup
Screen
No. for
Parameter
Group No.1
(Fig 4.1)
Parameter
Programming Range Default
EVO-
2212
EVO-
3012
EVO-
2224
EVO-4024 EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
1 “BULK CURRENT” (See NOTE 1)
(Bulk Charge Current “Io”)
0-100A 0-130A 0-70A 0-110A 40A
2 “ABSORP VOLTAGE”
(Absorption Voltage)
12.00V - 16.00V 24.00V - 32.00V 14.40V 28.80V
3 “EQUALIZE VOLTAGE”
(Equalization Voltage)
14.00V - 16.50V 28.00V - 33.00V 14.40V 28.80V
4 “FLOATING VOLTAGE"
(Float Voltage)
12.00V - 15.00V 24.00V - 30.00V 13.50V 27.00V
5 “COMPENSATE”
(Temperature Compensation)
3mV to 5mV /C/Cell 4mV /C/Cell
6 “BATT OVER VOLT”
(Battery Over Voltage Shutdown)
14.00V - 17.00V 28.00V - 35.00V 16.00V 32.00V
7 “RESET VOLTAGE”
(Reset voltage for "BATT LOW
VOLTAGE" condition)
12.00V - 17.00V 28.00V - 35.00V 14.00V 28.00V
8 “LOW VOLT ALARM”
(Battery Low Voltage Alarm)
9.50V to 13.50V 19.00V to 27.00V 11.00V 22.00V
9 “BATT LOW VOLTAGE”
(Battery Low Voltage Shutdown)
>9.00V to 13.00V >18.00V to 26.00V 10.50V 21.00V
10 “LV DETECT TIME”
(Time to qualify "BATT LOW
VOLTAGE" condition)
0 - 600 sec 10 sec
11 “LV CUT OFF TIME”
(Time in "BATT LOW VOLTAGE"
condition to trigger complete
shutdown)
0 - 7200 sec 1200 sec
12 “EQUALIZE-4STAGES”
(4 Stage Adaptive Equalization
On/ Off)
0 = No (3-Stage / 2-Stage)
1 = Yes (4-Stage Equalization)
0 = No (3-Stage / 2-Stage)
SECTION 4 | Parameter Setup