34 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 | Parameter Setup
4.4.2.11.2 Value of "LV CUT OFF TIME": 0 sec
4.4.2.11.2.1 When the value of parameter "LV CUT OFF TIME" is set at 0 sec, activation and resetting of Battery
low voltage!" fault condition (Section 7, Srl.1 of Table 7.1) will be as described in Section 4.4.2.9.2.
4.4.2.11.3 Programming Steps for Parameter "LV CUT OFF TIME"
Enter Key Enter Key Up Key x 10 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
L V C U T O F F T I M E
1 2 0 0 s e c
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
L V C U T O F F T I M E
1 2 0 0 s e c
4.4.2.12 EQUALIZE – 4 STAGES (Table 4.1, Parameter Setup Screen No. 12)
Please refer to Section 5.8.2 of EVO-2212/3012/2224/4024 Manual for background information on 4-Stage Adaptive
Charging Prole for Equalization
When AC input within the programmed window of voltage and frequency is available, EVO will operate as a battery
charger and charging will be carried out based on the selected option of parameter "CHARGING PROFILE". Parameter
"CHARGING PROFILE" (Section 4.4.2.21) allows option to select from 6 Charging Proles - 3 proles of 3-Stage and 3
proles of 2-Stage charging. Default prole option is "0=3 Stage Adaptive”
4-Stage Adaptive Charging Prole for Equalization can be activated AT ANY TIME through programmable parameter
"EQUALIZE-4STAGES" set to "1=Yes". The Default Setting is "0=No" i.e. charging will be carried out as per 3 or
2-Stage prole that has been selected by parameter "CHARGING PROFILE" (Section 4.4.2.21). After the 4-Stage
Adaptive Charging Prole for Equalization is completed, parameter "EQUALIZE-4STAGES" resets automatically to the
default setting i.e. Option "0=No" and the charging prole reverts to the last stage of the “CHARGING PROFILE” that
was active when 4-Stage Adaptive Charging Prole for Equalization was activated. Details are given at Table 4.2 below: