EasyManua.ls Logo

SamplexPower EVO-RC - Page 43

Default Icon
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMLEX AMERICA INC. | 43
APPENDIX A
TABLE 4.3 CHARGING PROFILE OPTIONS FOR 3 AND 2-STAGE CHARGING
Srl
No.
Options under
Programming Parameter
“CHARGING PROFILE”
(See setup procedure at
Section 4.4.2.21 in EVO-RC
Remote Control Manual
attached at Appendix A)
Charging Stages Battery Type
1
0 = 3 Stage Adaptive
(Shown as “0=3 Stg
Adaptive” in the
programming screen)
NOTES:
1. This is the default setting
2. This is a 3-Stage, Adaptive
Prole with “Adaptive
Time Algorithm” for the
Absorption Stage (For
details, refer to Section
5.7.2 of the attached
Owner’s Manual for EVO-
2212/3012/2224/4024)
1. Stage 1 – Bulk Stage (See Section 5.7.1.1 of the attached EVO-
2212/3012/2224/4024 Manual for details):
Charge at constant current = the programmed value of parameter “BULK
CURRENT” (Default value is 40A. For details of programming range & procedure, refer to Section 4.4.2.1
Transition to Absorption Stage when voltage rises to the set value for programming
parameter “ABSORP VOLTAGE” (Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-
2224/4024. For details of programming range & procedure, refer to Section 4.4.2.2)
2. Stage 2 - Absorption Stage (See Section 5.7.2 of the attached EVO-
2212/3012/2224/4024 Manual for details):
Charge at constant voltage = the programmed value for parameter “ABSORP
VOLTAGE”. (Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-2224/4024. For details of
programming range & procedure, refer to Section 4.4.2.2)
Adaptive Time Algorithm: Time in Absorption Stage is computed automatically
based on time in Bulk Stage (For details, refer to Section 5.7.2 of the Owner’s Manual for EVO-
2212/3012/2224/4024).
Transition to Float Stage thereafter.
3. Stage 3 - Float Stage (See Section 5.7.3 of the attached EVO-2212/3012/2224/4024
Manual for details):
Charge at constant voltage = the programmed value for parameter “FLOATING
VOLTAGE”.
(Default value is 13.5V for EVO-2212/3012 & 27.0V for EVO-2224/4024. For details of
programming range & procedure, refer to Section 4.4.2.4)
Reset to Bulk Stage under the following conditions:
i. If the AC input fails or is switched off and is restored subsequently.
ii. If battery voltage falls to the programmed value of parameter "RESET TO
BULK". (Default value is 12.0V for EVO-2212/3012 & 24.0V for EVO-2224/4024. For details of
programming range & procedure, refer to Section 4.4.2.15).
iii. If the charger remains in the Float Stage for 10 days
Lead Acid: Flooded
and sealed – AGM/
Gel Cell
ENSURE that there are
no other DC load(s)
on the batteries.
Load(s) on the battery
may drain full or
part of the charging
current and will
upset the “Adaptive
Time Algorithm” for
Absorption Stage time
2
1=3Stage Type1 1. Stage 1 – Bulk Stage (See Section 5.7.1.1 of the attached EVO-
2212/3012/2224/4024 Manual for details):
Charge at constant current = the programmed value of parameter “BULK
CURRENT” (Default value is 40A. For details of programming range & procedure, refer to Section 4.4.2.1)
Transition to Absorption Stage when voltage rises to the set value for programming
parameter “ABSORP VOLTAGE” (Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-
2224/4024. For details of programming range & procedure, refer to Section 4.4.2.2)
2. Stage 2 - Absorption Stage (See Section 5.7.2 of the attached EVO-
2212/3012/2224/4024 Manual for details):
Charge at constant voltage (CV) = the programmed value for parameter “ABSORP
VOLTAGE”. (Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-2224/4024. For details of
programming range & procedure, refer to Section 4.4.2.2)
Remain in Absorption Stage for time duration = programmed value of parameter
“ABSORP TIME” (Default value is 60 min. For details of programming range & procedure, refer to
Section 4.4.2.19)
Transition to Float Stage thereafter.
3. Stage 3 - Float Stage (See Section 5.7.3 of the attached EVO-2212/3012/2224/4024
Manual for details):
Charge at constant voltage = the programmed value of parameter “FLOATING
VOLTAGE”. (Default value is 13.5V for EVO-2212/3012 & 27.0V for EVO-2224/4024. For details of
programming range & procedure, refer to Section 4.4.2.4 )
Reset to Bulk Stage under the following conditions:
i. If the AC input fails or is switched off and is restored subsequently.
ii. If battery voltage falls to the programmed value of parameter "RESET TO
BULK". (Default value is 12.0V for EVO-2212/3012 & 24.0V for EVO-2224/4024. For details of
programming range & procedure, refer to Section 4.4.2.15).
iii. If the charger remains in the Float Stage for 10 days
Lead Acid: Flooded
and sealed – AGM/
Gel Cell
Lithium (See Section
5.11of EVO-
2212/3012/2224/4024
Manual for details)
SECTION 4 | Parameter Setup

Related product manuals