50 | SAMLEX AMERICA INC.
APPENDIX A
4.4.2.23.4 Programming Steps for Parameter "SAFE CHARGING"
Enter Key Enter Key Up Key x 22 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
S A F E C H A R G I N G
1 m i n
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
S A F E C H A R G I N G
1 m i n
4.5 GROUP 2 PARAMETER SET UP: INPUT SETTING
4.5.1 Programming Ranges & Default Values of Programming Parameters under Parameter Group
2 – INPUT SETTING
Refer to Parameter Group No.2 at Fig 4.1
Table 4.4 below gives details of programmable ranges & default values of parameters under Parameter Group No.2 -
"INPUT SETTING". Refer to Fig 4.1 under Section 4.1 for Menu Map for navigating through various parameters under
this Group No.2.
TABLE 4.4 Programming Information for Parameter Group No.2 - INPUT SETTING
Parameter
Setup Screen
No. for
Parameter
Group No.2
(Fig 4.1)
Parameter
Setting range Default value
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
1 DEFAULT FREQ 0 = 60Hz; 1 = 50Hz 0 = 60Hz
2 GRID MAX CURRENT 5 – 40A 5 – 70A 5 – 40A 5 – 70A 30A
3 GEN MAX CURRENT 5 – 40A 5 – 70A 5 – 40A 5 – 70A 30A
4 HIGH CUT OFF 50 – 70Hz 65Hz
5 HIGH RESET 50 – 70Hz 64Hz
6 LOW CUT OFF 40 – 60Hz 55Hz
7 LOW RESET 40 – 60Hz 56Hz
8
SYNC GRID
0=Fine
1=Coarse
0=Fine
9
SYNC GEN
0=Fine
1=Coarse
1=Coarse
10
INPUT OC PROTECT
0=INV mode
1=Shutdown
0=INV mode
11
INPUT RECOVERY
0=Buffered
1=Direct
0=Buffered
4.5.2 Description of Parameters under Parameter Group No.2 – INPUT SETTING
i
INFO
The values shown under various screenss are the Default Values for EVO-2212
SECTION 4 | Parameter Setup