52 | SAMLEX AMERICA INC.
APPENDIX A
current increases to a value of 1A more than the programmed value of "GEN MAX CURRENT" for 5 sec, input over
current protection will be activated based on option to either transfer to Inverting Mode or to shut down the EVO (Refer
to details of these 2 options under parameter INPUT OC PROTECT at Section 4.5.2.10):
4.5.2.3.1 Programming Steps for Parameter "GEN MAX CURRENT"
Enter Key Up Key Enter Key Up Key x 2 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
I N P U T S E T T I N G
ð
D E F A U L T F R E Q
0 = 6 0 H z
ð
G E N M A X C U R R E N T
3 0 . 0 0 A
ð
K E Y I N P A S S W O R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
G E N M A X C U R R E N T
3 0 . 0 0 A
4.5.2.4 HIGH CUT OFF (Table 4.4, Parameter Setup Screen No.4)
If the AC input frequency is over the value of “HIGH CUT OFF” when in "Charging Mode", the EVO™ Inverter/Charger
will transfer to Inverting Mode.
4.5.2.4.1 Programming Steps for Parameter "HIGH CUT OFF"
Enter Key Up Key Enter Key Up Key x 3 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
I N P U T S E T T I N G
ð
D E F A U L T F R E Q
0 = 6 0 H z
ð
H I G H C U T O F F
6 5 . 0 0 H z
ð
K E Y I N P A S S W O R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
H I G H C U T O F F
6 5 . 0 0 H z
4.5.2.5 HIGH RESET (Table 4.4, Parameter Setup Screen No.5)
This is the reset frequency at which the unit will revert to "Charging Mode" after it has switched over to "Inverter
Mode" due to input frequency rising above "HIGH CUT OFF".
4.5.2.5.1 Programming Steps for Parameter "HIGH RESET"
Enter Key Up Key Enter Key Up Key x 4 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
I N P U T S E T T I N G
ð
D E F A U L T F R E Q
0 = 6 0 H z
ð
H I G H R E S E T
6 4 . 0 0 H z
ð
K E Y I N P A S S W O R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
H I G H R E S E T
6 4 . 0 0 H z
4.5.2.6 LOW CUT OFF (Table 4.4, Parameter Setup Screen No.6)
If the AC input frequency is below “LOW CUT OFF” value when in "Charging Mode", the EVO™ Inverter/Charger will
transfer to Inverting Mode.
4.5.2.6.1 Programming Steps for Parameter "LOW CUT OFF"
Enter Key Up Key Enter Key Up Key x 5 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
I N P U T S E T T I N G
ð
D E F A U L T F R E Q
0 = 6 0 H z
ð
L O W C U T O F F
5 5 . 0 0 H z
ð
K E Y I N P A S S W O R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
L O W C U T O F F
5 5 . 0 0 H z
4.5.2.7 LOW RESET (Table 4.4, Parameter Setup Screen No.7)
This is the reset frequency at which the unit will revert to "Charging Mode" after it has switched over to "Inverting
Mode" due to input frequency falling below "LOW CUT OFF".
SECTION 4 | Parameter Setup