Characteristics
Flow characteristic with gradient
Gradient 0.2 to 3.2 [1.8]
Parallel displacement 30.0 to 30 [0] °C
Max. flow temperature 20 to 130 [90] °C
Min. flow temperature 20 to 130 [20] °C
Set-back for reduced operation 0 to 50 [15] °C
Return flow characteristic with gradient
Gradient 0.2 to 3.2 [1.2]
Parallel displacement 30.0 to 30 [0] °C
Max. return flow temperature 20 to 130 [65] °C
Min. return flow temperature 20 to 130 [65] °C
Limit values of the outdoor temperature
Summer time operation 0 to 50 [22] °C
Reduced operation 10 to 50 [15] °C
Rated operation 30 to 50 [15] °C
Set points for room temperatures
Rated operation 0 to 40 [20] °C
Reduced operation 0 to 40 [17] °C
Sustained temperature 0 to 40 [15] °C
Set points for drinking water heating
DW heating ON 20 to 90 [45] °C
DW heating OFF 20 to 90 [50] °C
Differential gap 0 to 30 [5] °C
Charging/drinking water temperature
20 to 90 [55] °C
End charging process 20 to 90 [53] °C
Return flow temp. limitation 20 to 90 [65] °C
Solar circuit pump ON 0 to 30 [10] °C
Solar circuit pump OFF 0 to 30 [2] °C
Solar charging OFF 20 to 90 [70] °C
Code number
1732