EB 5573 EN 16-47
Appendix A (conguration instructions)
Summer mode only becomes effective when the controller is in automatic mode ( ).
16.2.7 Delayed outdoor temperature adaptation
Thecalculatedoutdoortemperatureisusedtodeterminetheowtemperaturesetpoint.The
heat response is delayed when the outdoor temperature either increases or decreases or
both.Iftheoutdoortemperaturevariesby,forexample12°Cwithinaveryshortperiodof
time, the calculated outdoor temperature is adapted to the actual outdoor temperature in
smallsteps('Delayperhour'of3°C/h)overatimeperiodof
t=
12 C
3C/h
°
°
=4h
.
The delayed outdoor temperature adaptation helps avoid unnecessary overloads of central
heating stations in combination with either overheated buildings occurring, for example due
to warm winds or temporarily insufcient heating due to the outdoor sensor being exposed
to direct sunshine.
In the information level, the outdoor temperature blinks on the display while delayed outdoor
temperature adaptation is active. The calculated outdoor temperature is displayed.
Functions Default Conguration
Delayed outdoor temperature adaptation
as the temperature falls
0 CO5->F05-1
Delayed outdoor temperature adaptation
as the temperature rises
0 CO5->F06-1
3.0°C Delayperhour:0.2to6.0°C
Note
Note