16-50 EB 5573 EN
Appendix A (conguration instructions)
Functions Default Conguration
RoomsensorRF1/RF2 0 CO1,2->F01-1
Flash adaptation 0
20min
0.0
CO1,2->F09-1
Cycletime:0to100min
KP (gain): 0.0 to 25.0
Parameters Default Switch position: value range
Day set point 20.0°C
:0.0to40.0°C
Night set point 15.0°C
:0.0to40.0°C
16.2.11 Flash adaptation without outdoor sensor (based on room
temperature)
Theowtemperaturecontrolstartswith'Daysetpoint'forowinratedoperationorwith
'Nightsetpoint'forowinreducedoperationasnosetpointscalculatedusingcharacteris-
tics exist without an outdoor sensor. The 'Cycle time' determines the intervals at which the
owtemperaturesetpointiscorrectedby1°C.Theheatingisthenalwaysswitchedoffas
soonastheroomtemperatureexceedsthe'Daysetpoint'or'Nightsetpoint'by2°C.Heat-
ingrststartsagainwhentheroomhascooledoffandtheroomtemperatureis1°Cabove
thesetpoint.A'GainKP'settoavalueotherthan0causesadirectincrease/decreasein
owtemperaturesetpointwhenasuddendeviationinroomtemperaturearises.Werecom-
mend a 'Gain KP' setting of 10.0.
Functions Default Conguration
RoomsensorRF1/RF2 0 CO1,2->F01-1
Outdoor sensor AF1 1 CO1,2->F02-0
Flash adaptation 0
20min
0.0
CO1,2->F09-1
Cycletime:1to100min
KP (gain): 0.0 to 25.0
Parameters Default Switch position: value range
Day set point 20.0°C
:0.0to40.0°C
Night set point 15.0°C
:0.0to40.0°C
Parameters Default Parameter level: value range
Flow set point, day 50.0°C PA1,2:–5.0to+150.0°C
Flow set point, night 30.0°C PA1,2:–5.0to+150.0°C