2-4 EB 5573 EN
Markings on the device
Firmware revisions
Old New
2.48 2.51
MeaningofCO1,CO2->F02changed
F02--1=Outdoor-temperature-controlledcontrolactive
Buffer tank systems: the measured value SF1 is now also relevant to end charging
Discharging protection for DHW tank and buffer tank
Separateboostadjustableforunderoorheatingcircuits
Heatingcircuitscanbeconguredtobecircuitsonlyprocessingdemandwiththe
settingsCO1'->F00-1andCO2'->F00-1
Transmissionrangesettingfor0to10Vsignaltoprocessexternaldemandchangedto
CO5'->F07
Defaultsettingofheatingcharacteristic1.2(0.5forunderoorheating)
Defaultsettingofthemaximumowtemperature:70°C
Delayedoutdoortemperatureadaptationadjustableinstepsof0.1°C
2.51 2.61
New function Variable night set-backcanbeconguredseparatelyforeachheating
circuit (setting: CO1',CO2'->F04-1)
FunctionblocksCO1'->F03andCO4'->F03introducedtoactivatethedischarging
protection
Freeassignmentofanalogoutput:theCO5'->F10settingisusedtodeterminewhich
outputsignalistobeissuedatthe0to10Voutput.
2.61 2.63
Newsettingcongurable:14=3Vsupplyforanalogoutputs
2.63 3.00.xx
Harmonization of versions