EB 5573 EN 16-97
Appendix A (conguration instructions)
Pictogram
Parameter name
Value range (default setting)
Set point boost (primary exchanger control)
0.0to50.0°C(5.0°C)
Set point for binary demand processing
0.0to150.0°C(40.0°C)
Only in PA1 parameter level
Flow set point, day
–5.0to+150.0°C(50.0°C)
Onlywithashadaptationwithoutoutdoorsensor
Flow set point, night
–5.0to+150.0°C(30.0°C)
Onlywithashadaptationwithoutoutdoorsensor