EasyManua.ls Logo

Samson TROVIS 5573 - 9.4 Error status register

Samson TROVIS 5573
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 5573 EN 9-3
Malfunctions
9.4 Error status register
The error status register is used to indicate controller or system errors.
Error message Meaning Decimal value
Err1 Sensor failure 1 1
Err2 2
Err3 Disinfection temperature not reached 4
Err4 Max. charging temperature reached 8
Err5 16
Err6 Temperature monitor alarm 32 32
Err7 Unauthorized access occurred 64
Err8 Error message of a binary input 128
Err9 256
Total
Example: Value of error status register when a sensor fails and a
temperaturemonitoringalarm= 33