Installation Procedure
Step 14 optional : Setting the Emergency Temperature Output (ETO) function
Emergency Temperature Output (ETO) function (for the multi system, this function is not supported.)
CAUTION
In order to deploy the ETO function, the MIM-B14, an external contact interface module, must be installed in
each indoor unit.
The ETO is a concept of emergency operation of indoor units. If the indoor unit 1 (main indoor unit) stops
because of an error, the indoor unit 2 (sub indoor unit) starts to operate.
Basically, the indoor unit 2 operates in the previous mode. [For the first time operation, it starts in 75 °F (24
°C) Auto mode.]
To set more detailed operation conditions for the indoor unit 2, use the S-net Pro.
Setting up the ETO
1 Main indoor unit
Disable the external contact control (Default).
Connect the S-net pro2 to F1 and F2.
Enable the ETO function and set the temperature and time.
2 Sub indoor unit
(Reαuired) Enable the external contact control (with the installation option SEG14 - Reverse Control).
Connect the S-net pro2 to F1 and F2.
Enable the entrance control and set the mode, set temperature, and fan speed.
Communication between
indoor and outdoor units
(F1 and F2)
External contact
interface module
MIM-B14
Error output port
(1, 2)
Contact input port
(5, 6)
Main indoor unit
Sub indoor unit

Related product manuals