4-4 Samsung Electronics
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
4. Assign an indoor unit address by wireless remote controller.
-TheinitialindoorunitADDRESSissetas"MAIN:0,RMC:0".
-SetMainandRMCAddressonlythesettingisrequired.
-ThereisnoneedtoassigntheindoorunitMainAddressiftheoutdoorunitisaddressingautomatically.
TheindoorunitMainaddresswillfollowtheoutdoorunit'sautomatically.
-Assign 12 digit when setting the indoor unit address.
-NoneedtoassignSEG4,5,8,10whicharenonapplicable.Eventhoughthosesegmentsareset,theywillbeignored.
-If you set the applicable segments with numbers other than the indiciated, the initial setting will be maintained.
4-1-2
Setting an indoor unit address (MAIN/RMC)
•WhenA”~”F”isenteredtoSEG5~6,theindoorunitMAINADDRESSisnotchanged.
•IfyousettheSEG3as0,theindoorunitwillmaintainthepreviousMAINADDRESSevenifyouinputtheoptionvalueofSEG6.
•IfyousettheSEG9as0,theindoorunitwillmaintainpreviousRMCADDRESSevenifyouinputtheoptionvalueofSEG11~12.
OptionNo.:0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE SettingMainaddress
RESERVED RESERVED
The unit digit of
an indoor unit
Indication
andDetails
Indication
Details Indication
Details
Indication
Details
Indication
Details
0 A
0
NoMain
address
0~3
A single
digit
1
Mainaddress
setting mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation
PAGE
RESERVED
SettingRMCaddress
RESERVED
Group
channel(*16)
Group address
Indication
andDetails
Indication
Details
Indication
Details
Indication
Details
Indication
Details
1
0
NoRMCaddress
RMC1 0~2 RMC2 0~F
1
RMCaddress
setting mode
Example) If you want to set as "MAIN : 3, CHANNEL : 1, RMC : B",
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 A 1 - - 3
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 - 1 - 1 B
assign option codes except SEG 1, 7 which are page options.