Troubleshooting
4-17
4-3. Diagnostic Checklist ago
4-3-1. Test operation mode and check mode
Display Options key
Verify mode display
Pressing the K4 switch, you can view the following information about the system status
Short push Screen content SEG1 SEG2 SEG3 SEG4 Unit
1 Oder Frequency 1 Hundreds digit Tens digit Units digit Hz
2 Current Frequency 2 Hundreds digit Tens digit Units digit Hz
3 The number of current indoor units 3 Hundreds digit Tens digit Units digit Unit
4 The sensor for outdoor air intake 4 +/- Tens digit Units digit °C
5 Discharge sensor 5 Hundreds digit Tens digit Units digit °C
6 Eva-Mid sensor 6 +/- Tens digit Units digit °C
7 Cond sensor 7 +/- Tens digit Units digit °C
8 Current 8 Tens digit Units digit
The first place of
decimals
A
9 Fan RPM 9 Thousands digit Hundreds digit Tens digit rpm
10 Target discharge temperature A Hundreds digit Tens digit Units digit °C
11 EEV B Hundreds digit Tens digit Units digit step
12 The capacity sum of indoor units C Tens digit Unit digit
The first place of
decimals
kW
13 Protective control D
0: Cooling
1: Heating
Protective control
0: No Protective
control
1: Freezing
2: Non-stop
defrosting
3: Over-load
4: Discharge
5: Total electric
current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14 The temperature of heat radiating plate E Hundreds digit Tens digit Units digit -
15 S/W check F - - - -
Long push 1 Main micom version Year (Hex) month (Hex) Date (Tens digit) Date (Units digit)
After short push 1 Inverter micom version Year (Hex) month (Hex) Date (Tens digit) Date (Units digit)
After short push 1 E2P version Year (Hex) month (Hex) Date (Tens digit) Date (Units digit)
Press and hold the K4 button(The main micom version)
ĺ
Press once more shortly
ĺ
Press once more shortly(E2P version)
7-segment display
Key Switch
< AC090/100/120/140MXAD*H >
K3 switch
standby
mode(Eco Mode) release
KEY Push type Mode
Display
SEG1 SEG2 SEG3 SEG4
K1 Short
1st Heating test mode
2nd Defrost test mode
3rd Stop
K2 Short
1st Cooling test
2nd Inverter check
3rd Pump down
K3 Short 1st Reset Release Eco mode
Defrost test mode
Condition 1: The outdoor temperature is below 10°C.
Condition 2: All the temperature conditions should meetthe defrost conditions.