02 INSTALLATION
Ignition sources free
f Make sure to store the units in a place without continuously operating ignition sources (for example, open ames, an
operating gas appliance or an operating electric heater).
f The service engineers shall not use any ignition sources with the risk of re or explosion.
f Potential ignition sources shall be kept away from the work area where the ammable refrigerant can possibly be
released to the surrounding.
f The work area should be checked to ensure that there are no ammable hazards or ignition risks. The “No Smoking sign
shall be attached.
f Under no circumstances shall potential sources of ignition be used while in detection of leakage.
f Make sure that the seals or sealing materials have not degraded.
f Safe parts are the ones with which the worker can work in a ammable atmosphere. Other parts may result in ignition
due to leakage.
f Replace components only with parts specied by Samsung. Other parts may result in the ignition of refrigerant in the
atmosphere from a leak.
Area ventilation
f Make sure that the work area is well ventilated before performing a hot work.
f Ventilation shall be made even during the work.
f The ventilation should safely disperse any released gases and preferably expel them into the atmosphere.
f Ventilation shall be made even during the work.
Leakage detection methods
f The leakage detector shall be calibrated in a refrigerant-free area.
f Make sure that the detector is not a potential source of ignition.
f The leakage detector shall be set to the LFL (lower ammability limit).
f The use of detergents containing chlorine shall be avoided for cleaning because the chlorine may react with the
refrigerant and corrode the pipings.
f If leakage is suspected, naked ames shall be removed.
f If a leakage is found while in brazing, the entire refrigerant shall be recovered from the product or isolated (e.g. using
shut-o valves). It shall not be directly released to the environment. Oxygen free nitrogen (OFN) shall be used for purging
the system before and during the brazing process.
f The work area shall be checked with an appropriate refrigerant detector before and during work.
f Ensure that the leakage detector is appropriate for use with ammable refrigerants.
Labelling
f The parts shall be labelled to ensure that they have been decommissioned and emptied of refrigerant.
f The labels shall be dated.
f Make sure that the labels are axed on the system to notify it contains ammable refrigerant.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AE RXEDEG Series and is the answer not in the manual?

Samsung AE RXEDEG Series Specifications

General IconGeneral
BrandSamsung
ModelAE RXEDEG Series
CategoryHeat Pump
LanguageEnglish

Related product manuals