EasyManuals Logo

Samsung AE RXEDEG Series User Manual

Samsung AE RXEDEG Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
ENGLISH-25
02 INSTALLATION
Connecting the power terminal
f Connect the cables to the terminal board using the compressed ring terminal.
f Connect the rated cables only.
f Connect using a wrench which is able to apply the rated torque to the screws.
f If the terminal is loose, re may occur caused by arc. If the terminal is connected too rmly, the terminal may be
damaged.
Tightening Torque (kgf.cm)
M4 12~18
M5 20~30
For the product that uses the R-32 refrigerant, be cautious not to generate a spark by keeping the following
requirements:
- Do not remove the fuses with power on.
- Do not disconnect the power plug from the wall outlet with power on.
- It is recommended to locate the outlet in a high position. Place the cords so that they are not tangled.
CAUTION
Installing the earth wire
f Earthing must be done by your installation specialist for your safety.
f Use the earth wire by referring to the specication of the electric cable for the outdoor unit.
Earthing the power cable
f The standard of earthing may vary according to the rated voltage and installation place of the Air to Water Heat Pump.
f Earth the power cable according to the following.
Installation place
Power condition
High humidity Average humidity Low humidity
Electrical potential of lower than 150V Perform the earthing work 3.
Note 1)
Perform the earthing work 3 if
possible for your safety.
Note 1)
Electrical potential of higher than 150V
Must perform the earthing work 3.
Note 1)
(In case of installing circuit breaker)
Note 1) Earthing work 3
- Earthing must be done by your installation specialist.
- Check if the earthing resistance is lower than 100Ω. When installing a circuit breaker that can cut the electric circuit in
case of a short circuit, the allowable earthing resistance can be 30~500Ω.
f When using the terminal for earthing only f When using earthing of the switchboard
Earth
terminal
Distribution
Board

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AE RXEDEG Series and is the answer not in the manual?

Samsung AE RXEDEG Series Specifications

General IconGeneral
BrandSamsung
ModelAE RXEDEG Series
CategoryHeat Pump
LanguageEnglish

Related product manuals