Troubleshooting
Samsung Electronics 4-11
- Setting an indoor unit address and installation option
Setting an indoor unit installation option (suitable for the condition of each installation location
)
1. Check whether power is supplied or not.
-
When the indoor unit is not plugged in, there should be additional power supply
in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is 020010-100000-200000-300000.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 RESERVED
External room
temperature sensor
/ Minimizing fan
operation when
themostat is o
Central control
FAN RPM
compensation
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Drain pump Hot water heater Electronic heater
Opening the
electronic expansion
valve
Master / Slave
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output / External
heater On or o signal
S-Plasma ion Buzzer
Number of hours
using lter
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3
Individual control of a
remote controller
Heating setting
compensation
EEV opening of an
indoor unit stopped
during oil return or
Defrost operation.
- Human sensor
1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using lter(SEG18) will be set to '1000hour' even if the SEG18 is set to
exept for 2 or 6.
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as indoor 1.
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central control
option as 0 (Disuse) to exclude the indoor unit from the central control.
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
)
)
) )
9
9
/ 1
HOT
COIL
AC
POWER
OUTDOOR COM-
MUNICATION
Wire Remote
Controller
DC 12V
* The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit’s input Power)
COM1 COM2
(+) L N (-)
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
Indoor Unit
1(L)
F2
F1
2(N)