EasyManua.ls Logo

Samsung AM007FN1DCH/AA - MCU Branch Part Setup Error - Connect an Indoor Unit to a Branch Part Not Being Used

Samsung AM007FN1DCH/AA
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-69
4-4-35 MCU branch part setup error – Connect an Indoor unit to a branch part not being used
• Indoor unit connection to the unused branch part
Criteria
Cause of problem
• Occurs when MCU PIPE is turned off, yet an indoor unit is registered
Outdoor unit display
1. How to check
C
heck the actual use of the branch part. If it is used, turn on the Dip switch for branch part setup. After completing resetting, press
the outdoor unit's K3 button to reset or turn off to restart.
Indoor unit display
MCU BOX #1
MCU PCB
OFF
MCU address setup
ON
Indoor unit
Indoor unit address
Branch part use setup
4 4 2 1 5 6
0
Branch A
4
B
C D E
5
F
62
×(Operation)
(Timer)
(Fan)
(Filter)
×
(Defrost)

Table of Contents

Related product manuals