Samsung Electronics 2-43
Model
OAP Duct
AM072JNESCH/AA AM096JNESCH/AA
Power Supply φ,V,Hz 1,208~230,60 1,208~230,60
Mode
1)
-HP HP
Performance Capacity
Cooling
2)
Btu/hr 92%װ 72,000 96,000
Heating
3)
Btu/hr 92%װ 47,000 59,000
Power
Input Consumption (Cooling/Heating) W 105%ײ 360/360 450/450
Running Current (Cooling/Heating) A 105%ײ 2.60/2.60 3.10/3.10
Indoorunit refrigerant adding amount Kg/EA 1.18 1.18
Noise Level Actual Noise Pressure (High) dB(A)ײ 47 47
Fan
Type - Sirocco, Φ270*2EA Sirocco, Φ270*2EA
Motor
Model - DL-17860SSBA (DB31-00659A) DL-17860SSBA (DB31-00659A)
Type - BLDC Feedback BLDC Feedback
Output W - -
Fan Speed
Fan(H/M/L) 0 mmAq
rpm±20
875/-/- 890/-/-
Fan(H/M/L) Standard 1050/-/- 1080/-/-
Cooling (H/M/L) Standard - -
Heating (H/M/L) Standard - -
Airflow Rate
Fan(H/M/L)
/min
28.00/-/- 35.00/-/-
Cooling (High) - -
Heating (High) - -
Refrigerant
Type - R410a R410a
Control Method - EDM EEV 6.4C EDM EEV 6.4C
Temperature Control - Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse
External Static Pressure Standard (Min.~Max) mmH2O 25(5~30) 25(5~30)
Piping
Connections
Liquid (Flare)
Φ,mm 9.52 9.52
Φinch 3/8 3/8
Gas (Flare)
Φ,mm 19.05 22.23
Φinch 3/4" 7/8"
Drain
Φ,mm VP25 (OD 32,ID 25) mm VP25 (OD 32,ID 25) mm
Φinch - -
Weight
Net Weight kg 90 90
Shipping Weight kg 100 100
Dimensions
Net Dimensions (W×H×D)
mm 1465x460x910 1465x460x910
inch - -
Shipping Dimensions (W×H×D)
mm 1612 x 519 x 984 1612 x 519 x 984
inch - -
Bypass Tube
SOLENOID VALVE - Assy,FDF6A48 Assy,FDF6A48
Check VALVE - ID9.6-ID12.9 ID9.6-ID12.9
Panel Size
Model - - -
Net Weight kg - -
Shipping Weight kg - -
Net Dimensions (W×H×D) mm - -
Shipping Dimensions (W×H×D) mm - -
Functions
Auto restart - O O
Auto swing - X X
Group/Individual control - O(OAP group only) O(OAP group only)
External contact control - O O
Trouble shooting by LED - X X
Standard
accessories
Installation manual - O O
Operation manual - O O
Pattern sheet for installation - O O
Flexible drain hose - O O
Filter/Safety grille - X X
Drain pump
Drain pump - / Model Name Optional / MDP-G075SQ Optional / MDP-G075SQ
Max. lifting Height / Displacement mm / liter/h 750 / 24 750 / 24
Optional
Accessories
Wireless remote controller - MR-EH00U MR-EH00U
Wired remote controller - MWR-WE10N MWR-WE10N
External contact interface module - MIM-B14 MIM-B14
Duct Receiver kits - MRK-A10N MRK-A10N
EEV kits - - -
Indoor Unit(cont.)
QOAP Duct
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 35ఁDB, 28ఁWB - Outdoor temperature : 35ఁDB, 28ఁWB
*3) Norminal heating capacities are based on;
- Indoor temperature : 0ఁ DB, -3ఁWB - Outdoor temperature : 0ఁDB, -3ఁWB
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.

Table of Contents